Honeywell VR8305 Direct Ignition Combination Gas Control User Manual (2024)

Honeywell VR8305 Direct Ignition Combination Gas Control User Manual
Honeywell VR8305 Direct Ignition Combination Gas Control User Manual (1)

Contents hide

1Application

2Installation

2.1INSTALL ADAPTERS TO GAS CONTROL

2.2CHOOSE GAS CONTROL LOCATION

3WIRING

4Start-Up and Checkout

5CHECK SAFETY SHUTDOWN PERFORMANCE

6Maintenance

7INSTRUCTIONS TO THE HOME OWNER FOR YOUR SAFETY, READ BEFORE OPERATING:

8Documents / Resources

9Related Posts

Application

These direct ignition combination gas controls are used in gas-fired appliances with capacities up to 300 feet3/hour at 1 inch wc pressure drop [8.5 meters3/hour at 0.25 kPa] on natural gas. They include a manual valve, two automatic operators, and a pressure regulator. See Table 1 for temperature ranges and regulator types. VR8305 set up for natural gas includes a 393691 LP Conversion Kit. The kit contains a cap screw, a pressure regulator adjustment screw, a tapered spring and a conversion label.

CAPACITY:

Size(Inlet x Outlet)Capacity(at 1 inch wc pressure dropa)Minimum Regulated CapacityMaximum Regulated Capacity
1/2 x 1/2240 feet 3 /hour [6.8 meter 3 /hour]30 feet 3 /hour [0.8 meter 3 /hour]340 feet 3 /hour [9.6 meter 3 /hour]
1/2 x 3/4270 feet3 /hour[7.6 meter 3 /hour]30 feet 3 /hour[0.8 meter 3 /hour]370 feet 3 /hour[10.5 meter 3 /hour]
3/4 x 3/4300 feet 3 /hour[8.5 meter 3 /hour30 feet 3 /hour 0.8 meter 3 /hour]415 feet 3 /hour[11.8 meter 3 /hour]

Capacity based on 1000 Btu/feet 3 , 0.64 specific gravity natural gas at 1 inch wc pressure drop [37.3 MJ/meter 3 , 0.64 specific gravity natural gas at 0.25 k Pa pressure drop].

Use conversion factors in Table 3 to convert capacities for other gasses.

TABLE 1—TEMPERATURE RANGES AND REGULATOR TYPES.

Model NumberAmbient Temperature RangeRegulator Type
VR8305H0° F to 175° F

-18° C to +79° C]

Slow-opening
VR8305K-40° F to 175° F

[-40° C to +79° C]

Slow-opening
VR8305M-40° F to 175° F

[-40° C to +79° C]

Standard-opening
VR8305P-40° F to 175° F

[-40° C to +79° C]

Step-opening

APPROVALS:
American Gas Association design certificate:
UP-70-69A.
Canadian Gas Association design certificate:
UP-70-69A.
Australian Gas Association design certificate:
Applied for. Delta C: P-70-42A19

TABLE 2—FLANGE PART NUMBERS.

Inlet

Outlet

Pipe Size

Flange

Type

Part Number
Without

Hex

Wrench

With

Hex

Wrench

1/2 inch NPTStraight

Elbow

393690-6

393690-3

393690-16

393690-13

3/4 inch NPTStraight

Elbow

393690-4

393690-5

393690-14

393690-15

NOTE: Flange Kits include one flange with attached Oring and four mounting screws.

История вычислител...

История вычислительной техники

TABLE 3—GAS CAPACITY CONVERSION FACTORS

GasSpecific GravityMultiply Listed Capacity By
Manufactured0.600.516
Mixed

Propane

0.70

1.53

0.765

1.62

Installation

WHEN INSTALLING THIS PRODUCT…

  1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
  2. Check the ratings given in the instructions and on the product to ensure the product is suitable for your application.
  3. Ensure installer is a trained, experienced service technician.
  4. After installation is complete, use these instructions to check out product operation.

WARNING

FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR DEATH

Follow these warnings exactly.

  1. Disconnect power supply before wiring to prevent electrical shock or equipment damage.
  2. To avoid dangerous accumulation of fuel gas,turn off gas supply at the appliance service valve before starting installation, and perform Gas Leak Test after completion of installation.
  3. Always install sediment trap in gas supply line to prevent contamination of gas control.
  4. Do not force the gas control knob. Use only your hand to turn the gas control knob. Never use any tools. If the gas control knob will not operate by hand, the gas control should be replaced by a qualified service technician. Force or attempted repair may result in fire or explosion.

CAUTION

Never apply a jumper across or short the valve coil terminals. This may burn out the heat anticipator in the thermostat or damage the electronic direct ignition (DI) module.

IMPORTANT: These gas controls are shipped with protective seals over inlet and outlet tapping. Do not remove seals until ready to connect piping.

Follow the appliance manufacturer instructions if available; otherwise, use the Instructions provided below.

WARNING

FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR DEATH

  1. Do not use a gas control set for natural gas on LP gas or a gas control set for LP gas on natural gas.
  2. When making conversion, main and pilot burner orifices MUST be changed to meet appliance manufacturer specifications

VR8305 gas controls can be converted from one gas to another. To convert from natural gas to LP, use the 393691LP Conversion Kit that is included with the VR8305 Gas Control. To convert from LP to natural gas, use the 394588 Natural Gas Conversion Kit (order separately). Step-opening gas controls cannot be converted. To convert control from one gas to another:

  1. Turn off main gas supply to the appliance.
  2. Remove the regulator cap screw and pressure regulator adjusting screw.See Fig. 1.
    Honeywell VR8305 Direct Ignition Combination Gas Control User Manual (2)
    Fig. 1—Top view of gas control
  3. Remove the existing spring.
  4. Insert the replacement spring with tapered end down. See Fig. 2.
    Honeywell VR8305 Direct Ignition Combination Gas Control User Manual (3)
    Fig. 2—Installation of conversion kit in regulated gas control.
  5. 6. Check the regulator setting either with a manometer or by clocking the gas meter. Refer to Startup and Checkout.
  6. Install the new cap screw.
  7. Mount conversion label on control.
  8. Install control and appliance according to appliance manufacturer instructions

Honeywell VR8305 Direct Ignition Combination Gas Control User Manual (4)

Fig. 3—Install flange to gas control.

INSTALL ADAPTERS TO GAS CONTROL

Install adapters to gas control as follows:

Flanges

  1. Choose the appropriate flange for your application.
  2. Remove seal over gas control inlet or outlet.
  3. Ensure the O-ring is fitted in the flange groove. If the O-ring is not attached or is missing, do not use flange.
  4. With O-ring facing gas control, align the screw holeson the control with the holes in the flange. Insert and tighten the screws provided with the flange. See Fig. 3. Tighten the screws to 25 inch-pounds of torque to provide a gas-tight seal.

Bushings

  1. Remove seal over gas control inlet or outlet.
  2. Apply moderate amount of good quality pipe compound to bushing, leaving two end threads bare. On LP installation, use compound resistant to LP gas. Do NOT use Teflon tape.
  3. Insert bushing in gas control and thread pipe carefully into bushing until tight.

USING ADAPTERS TO SOLVE SWING RADIUS PROBLEMS

In some field service applications, it is difficult or impossible to thread the control onto the gas supply pipe because of space limitations. This problem can be resolved in many instances by using an adapter. The adapter in installed on the end of the supply pipe in place of the gas control, following the same precautions and instructions that are used for installing the gas control. After the adapter is installed, the gas control is attached to the adapter as outlined above. Note that using an adapter increases the overall length of the gas control.

CHOOSE GAS CONTROL LOCATION

Do not locate the gas control where it may be affected by steam cleaning, high humidity, dripping water, corrosive chemicals, dust or grease accumulation, or excessive heat. To ensure proper operation, follow these guidelines:

  • Locate gas control in a well ventilated area.
  • Mount gas control high enough above the cabinet bottom to avoid exposure to flooding or splashing water
  • Ensure the ambient temperature does not exceed the ambient temperature ratings for each component.
  • Cover gas control if appliance is cleaned with water, steam, or chemicals or to avoid dust and grease accumulation.
  • Avoid locating gas control where exposure is possible to corrosive chemical fumes or dripping water. Locate the gas control in the appliance vestibule on the gas manifold. In replacement applications, locate the gas control in the same location as the old gas control.

Install Piping to Gas Control

All piping must comply with local codes and ordinances or with the National Fuel Gas Code (ANSI Z223.1 NFPA No. 54), whichever applies. Tubing installation must comply with approved standards and practices

  1. Use new, properly reamed pipe free from chips. If tubing is used, ensure the ends are square, deburred and clean. All tubing bends must be smooth and without deformation.
  2. Run pipe or tubing to the gas control. If tubing is used, obtain a tube-to-tube coupling to connect the tubing to the gas control.
  3. Install sediment trap in the supply line to the gas control. See Fig. 4.
    Honeywell VR8305 Direct Ignition Combination Gas Control User Manual (5)
    Fig. 4—Install sediment trap.

Install Gas Control

  1. This gas control can be mounted 0-90 degrees, in any direction, including vertically, from the upright position of the gas control knob.
  2. Mount the gas control so gas flow is in the direction of the arrow on the bottom of the control.
  3. Thread pipe the amount shown in Table 4 for insertion into the gas control. DO NOT THREAD PIPE TOO FAR. Valve distortion or malfunction may result if the pipe is inserted too deeply into the gas control.
    TABLE 4—NPT PIPE THREAD LENGTH IN INCHES.
    Pipe

    Size

    Thread Pipe

    This Amount

    Maximum Depth

    Pipe Can Be

    Inserted Into Control

    3/89/163/8
    1/23/4½
    3/413/163/4
  4. Apply a moderate amount of good quality pipe compound (do not use Teflon tape) to pipe only, leaving two end threads bare. On LP installations, use compound resistant to LP gas. Refer to Fig. 5.
    Honeywell VR8305 Direct Ignition Combination Gas Control User Manual (6)
    Fig. 5—Use moderate amount of pipe compound
  5. Remove seals over gas control inlet and outlet if necessary
  6. Connect pipe to gas control inlet and outlet. Use wrench on the square ends of the gas control. If an adapter is used, place wrench on adapter rather than gas control. Refer to Figs. 1 and 6.
    Honeywell VR8305 Direct Ignition Combination Gas Control User Manual (7)
    Honeywell VR8305 Direct Ignition Combination Gas Control User Manual (8)
    Fig. 6—Proper use of wrench on gas control with and without flanges

WIRING

Follow the wiring instructions furnished by the appliance manufacturer, if available, or use the general instructions provided below. All wiring must comply with applicable electrical codes and ordinances.

Disconnect power supply before making wiring connections to prevent electrical shock or equipment damage.

  1. Check the power supply rating on the valve and ensure it matches the available supply. Install transformer, thermostat, and other controls as required.
  2. Connect control circuit to gas control terminals. See Figs. 1, 7 and 8.
    Honeywell VR8305 Direct Ignition Combination Gas Control User Manual (9)
    Fig. 7—VR8305 Wiring Connections in S87 Direct
    Ignition System.
    • POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
    • ALTERNATE LIMIT CONTROLLER LOCATION.
    • MAXIMUM IGNITER-SENSOR CABLE LENGTH: 3 ft. [.9 m] OR LESS.
    • 3 A REPLACEABLE FUSE.
    • ALARM TERMINAL PROVIDED ON SOME MODELS. M9043

      Honeywell VR8305 Direct Ignition Combination Gas Control User Manual (10)
      Fig. 8—VR8305 Wiring Connections in S89C Direct Ignition System

    • POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. MAKE SURE L1 AND L2 ARE NOT REVERSED; THIS WOULD PREVENT FLAME DETECTION.
    • ALTERNATE LIMIT CONTROLLER LOCATION.
    • SEN TERMINAL AND Q354 FLAME SENSOR ON D MODELS ONLY.
  3. Adjust thermostat heat anticipator to 0.70 rating stamped on valve operator.

Start-Up and Checkout

WARNING

FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR DEATH

  1. Do not force the gas control knob. Use only your hand to turn the gas control knob. Never use any tools.
  2. If the gas control knob will not operate by hand, the gas control should be replaced by a qualified service technician.

GAS CONTROL KNOB SETTINGS

The gas control knob has two settings: OFF prevents main burner gas flow. ON permits main burner gas flow. Under control of the thermostat and direct ignition module, gas can flow to the main burner.

NOTE: Controls are shipped with the gas control knob in the ON position

PERFORM GAS LEAK TEST

WARNING:FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR DEATH Check for gas leaks with rich soap and water solution anytime work is done on a gas control.

GAS LEAK TEST

  1. Paint all pipe connections upstream of the gas control with a rich soap and water solution. Bubbles indicate a gas leak.
  2. If a gas leak is detected, tighten the pipe connection.
  3. Stand clear while lighting main burner to prevent injury caused from hidden gas leaks that could cause flashback in the appliance vestibule. Light the main burner.
  4. With the main burner in operation, paint all pipe joints (including adapters) and gas control inlet and outlet with rich soap and water solution.
  5. If another gas leak is detected, tighten adapter screws, joints, and pipe connections.
  6. Replace the part if gas leak cannot be stopped.

TURN ON SYSTEM

Rotate the gas control knob counterclockwiseHoneywell VR8305 Direct Ignition Combination Gas Control User Manual (11) to ON

TURN ON MAIN BURNER

follow instructions provided by appliance manufacturer or turn thermostat up to call for heat.

  1. Do not exceed the input rating stamped on the appliance nameplate, or manufacturer recommended burner orifice pressure for the size
    orifice(s) used. Ensure the main burner primary air supply is properly adjusted for complete combustion (refer to the appliance manufacturer instructions).
  2. IF CHECKING GAS INPUT BY CLOCKING THE GAS METER:
    • Ensure that the only gas flow through the meter is that of the appliance being tested.
    • Ensure that other appliances are turned off and that their pilot burners are extinguished (or deduct their gas consumption from the meter reading).
    • Convert the flow rate to Btuh as described in the Gas Controls Handbook (form 70- 2602) and compare to the Btuh input rating on the appliance nameplate.
  3. IF CHECKING GAS INPUT WITH A MANOMETER (PRESSURE GAUGE):
    • Ensure the gas control knob is in the PILOT position before removing the outlet pressure tap plug to connect the manometer.
    • Turn the gas control knob back to PILOT when removing the manometer and replacing outlet pressure tap plug.
    • Shut off the gas supply at the appliance service valve, or for LP gas at the gas tank, before removing the outlet pressure tap plug and before disconnecting the manometer to replace the outlet pressure tap plug.
    • Perform the Gas Leak Test at the inlet pressure tap plug.

Standard-Opening and Slow-Opening PressureRegulator

  1. The gas control outlet pressure should match the manifold pressure listed on the appliance nameplate.
  2. With the main burner operating, check the gas control flow rate using the meter clocking method or check the gas pressure using a manometer connected to the gas control outlet pressure tap. Refer to Fig. 1.
  3. If necessary, adjust the pressure regulator to match the appliance rating. Refer to Table 5 or 6 for the factory set nominal outlet pressures and adjustment ranges.
    • Remove the pressure regulator adjustment cap and screw.
    • Using a screwdriver, turn the inner adjustment screw clockwiseHoneywell VR8305 Direct Ignition Combination Gas Control User Manual (12) to increase or counterclockwiseHoneywell VR8305 Direct Ignition Combination Gas Control User Manual (13) to decrease the main burner gas pressure.
      Outlet Pressure
      Nominal Factory
      Nominal InletSettingSetting Range
      Type ofPressureFullFull
      ModelGasRangeStepRateStepRate
      Standard-,Natural5.0 – 7.03.53.0 – 5.0
      Slow-openingLP12.0 – 14.010.08.0 – 12.0
      Step-Natural5.0 – 7.00.93.53.0 – 5.0
      openingLP12.0 – 14.02.210.08.0 – 12.0
      Outlet Pressure
      Nominal Factory
      Nominal InletSettingSettin g Range
      ModelType of
      Gas
      Pressure
      Range
      StepFull
      Rate
      StepFull
      Rate
      Standard-, Slow-openingNatural
      LP
      1.2 – 13
      2.9 3.9
      0.9
      2.7
      03 – 1.2
      2.0 – 3.0
      Step-Natural1.2 130.20.903 – 1.2
      openingLP2.9 – 3.90.92.72.0 – 3.0
    • Always replace the cap screw and tighten firmly to ensure proper operation.
  4. If the desired outlet gas pressure or gas flow rate cannot be achieved by adjusting the gas control, check the gas control inlet pressure using a manometer at the inlet pressure tap. If the inlet pressure is in the normal range (refer to Table 5 or 6), replace the gas control. Otherwise, take the necessary steps to provide proper gas pressure to the gas control.

Step-Opening Pressure Regulator

  1. The gas control outlet pressure should match the manifold pressure listed on the appliance nameplate.
  2. With the main burner operating, check the gas control flow rate using the meter clocking method or check the
    gas pressure using a manometer connected to the gas control outlet pressure tap. Refer to Fig. 1.
  3. If necessary, adjust the pressure regulator to match
    the appliance rating. Refer to Table 5 or 6 for factory set
    nominal outlet pressures and adjustment ranges.
    • Remove the pressure regulator adjustment cap screw.
    • Using a screwdriver, turn the inner adjustment screw
      clockwiseHoneywell VR8305 Direct Ignition Combination Gas Control User Manual (14) to increase or counterclockwiseHoneywell VR8305 Direct Ignition Combination Gas Control User Manual (15) to decrease the main burner gas pressure.
    • Always replace the cap screw and tighten firmly to
      ensure proper operation.
  4. If desired outlet pressure or flow rate cannot be achieved by adjusting the gas control, check the inlet pressure using a manometer at inlet pressure tap or upstream of the gas control. If the inlet pressure is in the normal range (refer to Table 5 or 6), replace the existing gas control. Otherwise, take the necessary steps to provide proper gas pressure to the gas control.
  5. Carefully check main burner lightoff at the step pressure. Ensure the main burner lights smoothly and without flashback to the orifice and that all ports remain lit. Cycle the main burner several times, allowing at least 30 seconds between cycles for the regulator to resume the step function. Repeat after allowing main burner to cool. Readjust the full rate outlet pressure, if necessary, to improve lightoff characteristics.

CHECK SAFETY SHUTDOWN PERFORMANCE

WARNING: FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR DEATH Perform the safety shutdown test any time work is done on a gas system.

NOTE: Read steps 1-7 below before starting and compare to the safety shutdown or safety lockout tests recommended for the direct ignition (DI) module. Where they differ, use the procedure recommended for the module.

  1. Turn gas supply off.
  2. Set thermostat or controller above room temperature to call for heat.
  3. Watch for ignition spark or for glow at hot surface igniter either immediately or following prepurge. See DI module specifications.
  4. Time length of igniter operation. See DI module specifications.
  5. After the module locks out, open gas control and ensure there is no gas flow to main burner.
  6. Set thermostat below room temperature and wait one minute.
  7. Operate system through one complete cycle to ensure all controls operate properly

Maintenance

WARNING: FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR DEATH Improper cleaning or reassembly may cause gas leakage. When cleaning, ensure that control is reassembled properly and perform gas leak test.

Regular preventive maintenance is important in applications that place a heavy load on system controls, such as in the commercial cooking and agricultural and industrial industries because:

  • The equipment operates 100,000-200,000 cycles per year in many such applications, particularly commercial cooking. Such heavy cycling can wear out the gas control in one to two years.
  • Exposure to water, dirt, chemicals and heat can damage the gas control and shut down the control system.
    The maintenance program should include regular checkout of the gas control, see Start-Up and Checkout, page 6, and the control system as described in the appliance manufacturer’s literature.

Maintenance frequency must be determined individually for each application. Some considerations are:

  • Cycling frequency. Appliances that may cycle 100,000 times annually should be checked monthly.
  • Intermittent use. Appliances that are used seasonally should be checked before shutdown and again before the next use.
  • Consequence of unexpected shutdown. Where the cost of an unexpected shutdown would be high, the system should be checked more often.
  • Dusty, wet, or corrosive environment. Since these environments can cause the gas control to deteriorate more rapidly, the system should be checked more often. The gas control should be replaced if:
  • It does not perform properly on checkout or troubleshooting.
  • The gas control knob is hard to turn or push down, or it fails to pop back up when released.
  • The gas control is likely to have operated for more than 200,000 cycles.

WARNING: FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE, SEVERE, INJURY, OR DEATH Do not disassemble the gas control; it contains no replaceable components. Attempted disassembly or repair may damage the gas control.

CAUTION: Do not apply a jumper across or short the valve coil terminals. Doing so may burn out the heatanticipator in the thermostat or damage the DI module.

IMPORTANT: Allow 60 seconds after shutdown before re-energizing step-opening model to ensure lightoff at step pressure.

IF MAIN BURNER WILL NOT COME ON WITH CALL FOR HEAT:

  1. Ensure gas control knob is in the ON position
  2. 2. Adjust thermostat several degrees above room temperature.
  3. Using ac voltmeter, measure voltage across MV terminals at gas control.
  4. If no voltage is present, check control circuit for proper operation.
  5. If proper control system voltage is present, replace gas control.

INSTRUCTIONS TO THE HOME OWNER FOR YOUR SAFETY, READ BEFORE OPERATING:

FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR DEATH

Follow these warnings exactly:

  1. Pilot flame is lit automatically. Do not light the pilot flame manually.
  2. Before lighting pilot burner flame, smell around the appliance for gas. Be sure to smell next to floor because LP gas is heavier than air.
  3. IF YOU SMELL GAS:
    • Turn off the gas supply at the appliance service valve. On LP gas systems, turn off gas supply at the gas tank.
    • Do not light any appliances in the house.
    • Do not touch electrical switches or use the phone.
    • Leave the building and use a neighbor’s phone to call your gas supplier.
    • If you cannot reach your gas supplier, call the fire department.
  4. Do not force the gas control knob. Use only your hand to push down or turn the gas control knob. Never use any tools. If the gas control knob will not operate by hand, the gas control should be replaced by a qualified service technician. Force or attempted repair may result in a fire or explosion.
  5. The gas control must be replaced in case of any physical damage, tampering, bent terminals, missing or broken parts, stripped threads, or evidence of exposure to heat.

IMPORTANT: Follow the operating instructions provided by the manufacturer of your heating appliance. The information below will be of assistance in a typical control application, but the specific controls used and the procedures outlined by the manufacturer of your appliance may differ, requiring special instructions.

STOP: READ THE WARNINGS ABOVE.

The pilot flame is lit automatically. If the appliance does not turn on when the thermostat is set several degrees above room temperature, follow these instructions.

  1. Set the thermostat to its lowest setting to reset the safety control.
  2. Disconnect all electric power to the appliance.
  3. Remove the gas control access panel.
  4. Push in the gas control knob slightly and turn
    clockwiseHoneywell VR8305 Direct Ignition Combination Gas Control User Manual (16)to OFF.
  5. Wait five minutes to clear out any unburned gas. If you then smell gas, STOP! Follow step 3 in the WARNING above. If you do not smell gas, continue with the next step.
  6. Turn the gas control knob counterclockwiseHoneywell VR8305 Direct Ignition Combination Gas Control User Manual (17) to ON.
  7. Replace the gas control access panel.
  8. Reconnect all electric power to the appliance.
  9. Set the thermostat to the desired setting.
  10. If the appliance does not turn on, set the gas control knob to OFF and contact a qualified service technician for assistance.

TURNING OFF THE APPLIANCE

VACATION SHUTDOWN—Set the thermostat to the desired room temperature while you are away. COMPLETE SHUTDOWN—Push the gas control knob in slightly and turn clockwiseHoneywell VR8305 Direct Ignition Combination Gas Control User Manual (18) to OFF. Do not force. Appliance will completely shut off. Follow the lighting procedures above to resume normal operation.

Residential and Building Controls Division Honeywell Inc. 1985 Douglas Drive North Golden Valley, Minnesota 55422

Residential and Building Controls Division Honeywell Limited—Honeywell Limitée 740 Ellesmere Road Scarborough, Ontario M1P 2V9

Helping You Control Your World
Honeywell VR8305 Direct Ignition Combination Gas Control User Manual (19)

Documents / Resources

Honeywell VR8305 Direct Ignition Combination Gas Control [pdf] User Manual
VR8305, Direct Ignition, Combination Gas Control

Related Posts

  • Hearthstone DVI44 Gas-Fired Direct-Vent Insert User Manual

    Hearthstone DVI44 Gas-Fired Direct-Vent Insert User Manual - Optimized PDF Hearthstone DVI44 Gas-Fired Direct-Vent Insert User Manual -…

  • Valor G3.5 Direct Vent Insert Gas Fireplace Installation Manual

    Valor G3.5 Direct Vent Insert Gas Fireplace Installation Manual - Optimized PDF Valor G3.5 Direct Vent Insert Gas…

  • Honeywell Portable Single Gas Detector User Manual

    Gas Detection Quick Reference GuideHoneywell BW ™ Solo Portable Single gas Detector ©2020, Oct 23 G05-4001-000-RevC Overview Contact…

  • Honeywell C437F1052 Auto Recycle Gas/ Air Pressure Switch Installation Guide

    This is a legacy product document supported by Resideo. It is no longer manufactured Pressure Switch Installation Addendum…

Honeywell VR8305 Direct Ignition Combination Gas Control User Manual (2024)

FAQs

What is the C on a Honeywell gas valve? ›

File Number. Honeywell Gas Valve Nomenclature. Opening Characteristic. A, M = Standard. C, P = Step Open.

What is automatic combination gas valve? ›

Automatic combination gas valve. A gas valve for gas furnaces that incorporates a manual control, gas supply for the pilot, adjustment and safety features for the pilot, pressure regulator, and the controls for and the main gas valve.

What is C valve? ›

A double eccentric C-ball valve is similar in principle to a conventional ball valve, but with a half ball that makes a “C” shape. This C-shaped ball rotates on two planes of motion with energy from the stem to close and seal against a fixed seat.

What does C stand for on a Honeywell thermostat? ›

Known as the common wire, (C-Wire) provides WiFi thermostats continuous power from heating (e.g. furnaces) and cooling systems (e.g. Air Conditioning systems).

What position should gas valve be in? ›

The gas meter and gas service shutoff valve is usually located on the side or in front of the building. If the building has a breezeway, it could be located there.

What position should a gas valve be for open? ›

When the long side of the nub or handle is parallel to the incoming gas line, it's open and the gas is flowing. When it's turned a quarter turn, perpendicular to the incoming pipe, it's closed.

How do you know if the gas valve is not working? ›

If 24 volts is coming from the board to the gas valve terminals and you don't hear that little clicking noise the internal valve makes, you could have a bad gas valve. To double-check, take the leads off to the gas valve and check there. Got 24 volts? Then something downstream of that 24 volts is not working.

What is normal gas valve pressure? ›

Typical gas manifold pressure on natural gas is usually set between 3.2”WC – 3.7”WC. Manifold pressure is the gas pressure that the gas valve delivers to the burners, to supply the BTU's.

What are the 3 types of automatic gas valves? ›

All of the most common types of automated valves fall into one of three main categories. They are linear, rotary, and self-actuated. There are a variety of valve types within each of these categories each having its own benefits.

How many valves does a combination gas valve have? ›

The Combination Gas Control Valve incorporates dual gas shut-off valves and a negative-pressure regulator. The nega- tive-pressure regulator controls the outlet pressure to slight- ly below the reference pressure supplied to the regulator diaphragm by the vent line.

What is the difference between air valve and air release valve? ›

Air release valves have smaller openings and can automatically release air pockets during normal system operation. Air/vacuum valves admit and release large amounts of air during pipeline filling and draining while combination air valves do the function of both an air release and a air/vacuum valve.

What is the difference between Cv and flow? ›

The larger the Cv, the larger the flow at a given pressure differential. By definition, a Cv value of one is the Cv required to flow one gallon per minute (gpm) of water at 60' F with a pressure differential of one psi. Flow is proportional to the value of Cv.

How do you know if your a C thermostat is working? ›

You'll most likely hear a quiet clicking sound followed by air moving through the ductwork. You can also place your hand on a vent to feel for hot or cold air. If you don't hear or feel anything within a minute or two of making the changes, your thermostat may need to be replaced.

Do I need to use the C wire on my thermostat? ›

While your thermostat may not technically need a C-wire to operate, it gets the power for its screen and Wi-Fi capabilities through “phantom power” or “power stealing.” Basically, this means your thermostat gets a kick of extra power whenever your HVAC system is running.

How do you tell if a valve is open or closed? ›

If the handle on top is parallel to the valve, it's open. Likewise, if the handle is perpendicular to the top, the valve is closed. Common places you might find a ball valve are in irrigation and in sites where you need to control water supply from one area to another.

What valve is used for gas? ›

Gate Valves

The gate valve may be the most commonly used in the industry. It uses a gate system to open or close a pipeline entirely. This is an excellent choice if the flow rate needs to be controlled and maintained.

Is it bad to leave gas valve open? ›

But leaving the tank valve on is not advisable, for safety reasons. Always turn it off. The gas inside will continue to leach out resulting in loss of volume of fuel in the container.

Should gas lever be up or down? ›

In newer houses, the isolation valve is normally outside with the gas meter - in a meter box. If it's not there, try looking under the stairs, beneath the kitchen sink or in the garage. Turn the handle so the lever is at 90 degrees to the upright gas pipe.

Which way should a lever valve go? ›

OPERATION. The valve handle is marked showing proper rotation direction for “ON” and “OFF” positions. Rotation is clockwise for “OFF” (closed) and counter clockwise for “ON” (open). You can control the flow by moving the lever between 0° and 90°.

Why does my gas valve click but no flame? ›

Most likely, your furnace is making a clicking noise and not providing heat because your furnace's spark igniter is trying to ignite your pilot light or burners but is failing to do so. In other words, there's an ignition system malfunction that needs to be fixed. Otherwise, your furnace won't start.

Why is my gas valve not letting gas through? ›

So what causes gas valve failure? Gas valves get worn out over time, or they can get damaged by excessive basem*nt moisture or water seepage. However, there could be other culprits. A faulty ignitor, circuit board, or thermocouple could also keep your furnace from creating heat.

What happens if gas pressure is too low? ›

If the gas pressure is too low, your furnace's efficiency will go down. Not only that, but it will lead to a greater amount of condensation of burned gases. That is because the proportion of air in the air-fuel mixture will be too great.

How do I know if I have enough gas pressure? ›

Acceptable Gas Line Pressure Drop

Typically, if the gas line loses approximately 2 psi from a test of 20 psi on the line, the lines are acceptable. Conversely, if the line loses more than 10% of the pressure, it may have a leak. This can be true after a 30 minute or even a 24 hour test.

What does a Honeywell gas valve do? ›

The Honeywell gas valve is a gas distribution device. When there is a need for more gas in the burner, a signal is sent from the printed circuit board to the gas valve, which opens and allows gas to flow through the valve into the pilot assembly or the burner, depending on the model.

How do you tell if you have a bad gas valve on a furnace? ›

Symptoms of a Malfunctioning Furnace Gas Valve
  1. No Heat. A malfunctioning furnace gas valve may impede your furnace's ability to perform the combustion process. ...
  2. Constant Furnace Cycling. Inadequate gas flow from the valve may cause your furnace to stay on for an extended period of time. ...
  3. Carbon Monoxide Alarm.
Dec 29, 2021

What is the difference between a gas valve and a gas regulator? ›

In the simplest terms, a valve controls flow and a regulator controls pressure. Since the use of process fluid pressure is a means for control, regulators are functional as pressure control valves. Another difference comes in relation to the design pressure rating of the body of the regulator.

How long does a gas valve last? ›

What is the typical number of years of operation before a replacement is required? Gas Valves are routinely checked for 100,000 cycles and are used in equipment that have approximately 15 years life expectancy.

Why is it called a combination gas valve? ›

Combination gas valve: This type of gas valve was introduced around the 1960s. A combination gas valve contains a handle, a thermocouple, a regulator, and a solenoid valve. In essence, it contains everything needed for the operation of a gas fired furnace.

What are the symptoms of a shortage of primary air? ›

Symptoms and Causes
  • Restlessness.
  • Headache.
  • Confusion.
  • Anxiety.
  • Rapid heart rate (tachycardia).
  • Rapid breathing (tachypnea).
  • Difficulty breathing or shortness of breath (dyspnea).
May 12, 2022

Why do we use a thermocouple on a combination gas valve? ›

The thermocouple in a gas furnace is designed to keep the gas valve open through its electric voltage. If the pilot light goes out, the loss in heat causes the voltage between the two pieces of metal to drop, and this shuts the valve and reduces the combustion risk.

How often should the vent or stack on a gas heater be checked? ›

A gas furnace should be serviced at least once a year, preferably, though, in both the spring and the fall. Annual maintenance, including a thorough examination and cleaning of the parts that commonly malfunction, like the air filter, the fan, the pilot light, and the heat exchanger, can usually prevent these problems.

What controls the gas valve on a furnace? ›

The thermocouple (or thermopile) generates the power holds the safety valve open. Additionally, the thermocouple remains immersed in the pilot light flame. Without adequate heating of the thermocouple or thermopile, the furnace gas valve closes.

What does C mean on furnace? ›

The C wire is an extra wire that is used to create a continuous 24V power loop between your thermostat and the rest of the HVAC system. It allows the power to be used for any application and allows more advanced thermostats to function to their highest potential. C stands for common and it's usually labeled as C.

What is the C on a furnace? ›

What Is A C-Wire? A C-wire, or a common wire, runs from your low voltage heating system (24v) and carries continuous power to your thermostat. In today's electric market, most newer heating and cooling systems have C-wires, which guarantees compatibility for the installation of all smart thermostats.

What purpose does the C terminal on a furnace control board perform? ›

The C-terminal is the 24 volt common (as opposed to hot). This terminal is necessary to power thermostat as the thermostat needs a source of power to operate. This terminal is kind of like the neutral side of a 120-volt circuit.

What is the ABC setting on a Honeywell water heater? ›

Generally, A means 120 degrees, B means 130 degrees, and C means 140 degrees.

Should you use AC for heat? ›

Therefore, the AC should always be on in most cars (even in the winter). Most cars are actually DESIGNED for the A/C and heater to run together. When you run the A/C and heater simultaneously the A/C compressor is energized and the evaporator coil (under the dash) removes moisture from the air.

What should my AC thermostat be set at? ›

Energy.gov suggests that 68 degrees is a good room temperature while you're awake at home but recommends lowering it while you're asleep or away. Lowering your thermostat 7-10 degrees for eight hours a day can reduce your annual heating expenses by as much as 10 percent.

What does C stand for in heat transfer? ›

The symbol c stands for specific heat, and depends on the material and phase. The specific heat is the amount of heat necessary to change the temperature of 1.00 kg of mass by 1.00 ºC.

What if my furnace has no C terminal? ›

If there is no hidden C-wire, you can use a G-wire instead. However, you will not be able to use your fan independently when the heating or cooling isn't running. Also, many HVAC systems are incompatible with this solution, including: HVAC systems using electric heat.

Is the C wire positive or negative? ›

Thermostats like the Honeywell Wi-Fi Smart, the Honeywell Wi-Fi Smart with Voice Control and the Ecobee3 enlist help from the C-wire, a fifth or extra wire that provides the negative charge needed to supply enough power for those newer features.

What is the C terminal on a gas furnace? ›

The c wire is an extra wire that can be used to provide a return path for continuous 24V power for any application. It's normally used to provide a return path to power the thermostat. The “c” stands for common. It is often labeled as “c” on thermostat backplates.

Is the C wire a ground? ›

A: C stands for common. The common wire is the ground or negative wire. To complete the circuit that provides power to the thermostat you need a positive and negative wire from the 24V transformer.

What does A and B mean on a water heater? ›

Most hot water heaters have a A-B-C knob. Here is what temperature each letter stands for: Hot- 120 degrees. A- 130 degrees. B- 140 degrees.

How do I set my Honeywell heater control? ›

How to Set the Temperature of Your Honeywell Thermostat. If you have a manual thermostat, setting the temperature on your Honeywell thermostat is simple. All you need to do is to press the up and down buttons to set the temperature. The temperature you set will stay until you change the temperature again.

Is 140 too hot for water heater? ›

The best temperature setting for a hot water heater is between 120 and 140 degrees. Below 120 degrees, bacteria can develop in the stagnant water sitting in the tank. Above 140 degrees, the water is so hot that you and family members can be at risk for scalding in as little as two seconds.

References

Top Articles
Latest Posts
Article information

Author: Prof. An Powlowski

Last Updated:

Views: 6255

Rating: 4.3 / 5 (64 voted)

Reviews: 95% of readers found this page helpful

Author information

Name: Prof. An Powlowski

Birthday: 1992-09-29

Address: Apt. 994 8891 Orval Hill, Brittnyburgh, AZ 41023-0398

Phone: +26417467956738

Job: District Marketing Strategist

Hobby: Embroidery, Bodybuilding, Motor sports, Amateur radio, Wood carving, Whittling, Air sports

Introduction: My name is Prof. An Powlowski, I am a charming, helpful, attractive, good, graceful, thoughtful, vast person who loves writing and wants to share my knowledge and understanding with you.